10 exam-style questions with answers and explanations, straight from our 1,030-question bank. Tap an answer to check yourself. When you're ready, take the scored version in the free practice test.
These 10 free CSME questions are organized by exam domain, so you can see how each part of the Certified Subject Matter Educator - Gas Heat blueprint is tested. Reveal the answer and explanation under each question.
Domain 1: Combustion theory
Question 1
Two flue-sampling ports on a draft-hood appliance give simultaneous dry readings: before dilution-air entry, 120 ppm CO and 5.0% O2; downstream of the hood, 60 ppm CO and 13.0% O2. Burner input is steady. What accounts for this change between locations?
Show answer & explanation
Correct answer: A - Air entering after combustion dilutes the measured CO concentration.
Question 2
Meter clocking a single-stage furnace running continuously at full fire gives 2.00 ft³ in 84 seconds, with every other gas load off. Its nameplate rates input at 100,000 Btu/h, and its AFUE is 80%. The utility heating value is 1,050 Btu/ft³, and applicable meter corrections are already included. What does the meter test establish?
On a furnace diagram, the 24-V circuit runs from transformer R through a thermostat contact, then relay coil X-Y, and back to transformer C. During a heat call, readings are R-C = 24 VAC, X-C = 24 VAC, Y-C = 24 VAC, and X-Y = 0 VAC. There is one open circuit and no parallel feed path. Locate the open.
Show answer & explanation
Correct answer: D - An open return conductor from Y to transformer terminal C.
Question 4
The pilot on an interrupted-pilot boiler extinguishes when the control ends the main-flame establishing period. The main burner stays stable, its separate flame signal remains proven, and all operating limits are normal. The pilot valve is confirmed de-energized at the commanded time. How should the technician respond?
Show answer & explanation
Correct answer: D - Let the firing cycle continue while observing operation.
Question 5
An intermittent-pilot appliance lights its pilot and stops sparking, but its main burner stays off. A properly performed flame-proving test shows a steady 2.4 µA DC against a required minimum of 1.0 µA. Test wiring has been restored, and the heat call, supply voltage, and interlocks are verified. Which measurement would distinguish a missing main-valve command from a gas-delivery problem?
Show answer & explanation
Correct answer: C - The voltage across the main gas-valve coil while the control should energize it.
Domain 3: furnace installation and service
Question 6
Identify the vent category for a furnace with these listed characteristics: an induced-draft fan, nonpositive vent pressure, and flue temperatures high enough to avoid excessive condensate.
Show answer & explanation
Correct answer: B - Category I
Question 7
After a furnace replacement, an atmospheric water heater is the only appliance left on their formerly shared masonry chimney. The new furnace vents separately, and the unused chimney opening is sealed. Before signing off the water heater's continued use, what must the contractor do?
Show answer & explanation
Correct answer: A - Check chimney sizing and verify venting with the water heater operating alone.
Domain 4: troubleshooting
Question 8
Heat delivery falls when other gas appliances start. The furnace requires 5-10 in. w.c. at its gas-valve inlet: it measures 7 in. w.c. with no appliances firing, but 3 in. w.c. under the combined load. The main-valve coil receives its required 24 VAC, yet manifold pressure is low. Where should the investigation turn?
Show answer & explanation
Correct answer: C - The upstream gas supply under combined appliance load.
Question 9
A filter replacement has not stopped a furnace from cycling on its high-temperature limit. The service record shows rated gas input, the approved heating-blower setting, a 75°F temperature rise against a 35-65°F allowance, and 0.80 in. w.c. external static pressure against a 0.50-in. maximum. Which follow-up is supported by this combination?
Show answer & explanation
Correct answer: A - Check air-path resistance and establish the actual delivered airflow.
Domain 5: safety
Question 10
During a residential furnace service visit, a CO alarm sounds and an occupant reports headache and nausea. The furnace has just shut off on its thermostat. What should the technician do first?
Show answer & explanation
Correct answer: C - Get the occupants outdoors, then call emergency services from a safe location.
That's 10 of 1,030
The full bank has 1,020 more CSME questions with explanations.